Samwha-Dsp SOPR-3DE Digital Overload Relay Motor Protector Thermal Overload Relay
General
SOPR-3DE series digital overload and phase lost relays are designed toprevent the failures originated from motor heat.
Setting
D-Time: Set two to three seconds longer than the motor starting time.O-Time: Over-current run time.Set less than the motor's endurance time with over-current.LOAD: Set over 110% of the motor started current or under 120% of its operating current.
Relay Condition
When Powered: 95(COM) and 96(NC)is open circuit,95(COM)and 98(NO) is short circuit.When Tripped: 95(COM) and 96(NC) is short circuit, 95(COM)and 98(NO) is open circuit.
Configuration Menu
Trip Cause Indication
Maintenance
Periodic testing of TEST button is recommended to ensure the full protectionand regularly as preventive maintenance.Switch off the device and release from connections.Clean the trunk of device with a swab.Don't use any conductor or chemical might damagethe device.Make sure device works after cleaning.
Specifications
Current Range............ : Type05) 1-6A Type30) 5-30A Type60) 5-60A Type120) 10-120aOperating Voltage(Un): Tpye24) 24VAC/DC Tpye220) 90-260VACOperating Frequency....: 50/60HzOperating Power...........: <2WOperating Temperature: -20℃·····+55℃Waiting(t)......................: D-Time 1-30s O-Time 1-10sAsymmetry Set.............: %±1Contact.........................: 5A 250VAC Resistive LoadConnection Diagrams..: 35mm Din Rail(D) or Pane(P)
Dimensions
Connection Diagram
is_customized : Yes
Origin : Mainland China
Power Source : AC
Certification : CE
Protect Feature : Sealed
Brand Name : samwhadsp
Model Number : SOPR-3DE
Contact Load : Low Power
Usage : Protective
Theory : Thermal Relay
Main Circuit Wiring : Through Core
Current Range(A) : 0.5-6A / 3-30A / 5-60A / 10-120A
Protected object : motor
Relay output : 1c